Programmable Logic
Controller Basics
EET3370 Lab 1
Name
SAFETY:
The
industrial trainers are equipped with ground fault interrupters which are
designed to detect small currents to ground and interrupt the circuit. These do not eliminate the possibility
of electrical shock. While performing
control wiring on the trainers, the circuit breaker should be turned OFF and
only turned ON when you are ready to test the wiring. The back of the panel has exposed wiring and
120 volt ac potentials are present when the trainers are plugged in.
For
wiring purposes the 120 volt ac line and the neutral are brought out to two
busses on the lower portion of the trainer panel. Other busses labeled B1 thru B4 can be used
as tie points.
At
the end of the lab period remove power to the trainers by disconnecting the
trainer from the supply receptacle. When
working in groups, make sure that all members know when the trainers are
energized.
RELAY
LOGIC GATES:
1. With the power turned off and using an
ohmmeter, determine the contacts and operation of the push buttons and selector
switches on the industrial trainer.
2. The basic building block of a relay ladder
diagram or relay logic is the relay. It
consists of a coil which when energized causes a group of contacts to change
states. For example, if a contact was
opened it would close or if a contact was closed it would open. It is very important to realize that relay
ladder diagrams are shown in the de-energized state. In other words the contacts are shown as if
there was no power applied to the circuit.
Contacts are called "normally opened" or "normally
closed" depending on their state when the relay is de-energized.
We
will examine the operation of relays by wiring the circuit per the ladder
diagram attached. Do not put the dotted contact
connections in at this time.
The contact on line 4 is a normally opened
contact and the contact on line 5 is a normally closed contact. Fill in the table below by energizing and
de-energizing the coil of CR1 and observing the lights in series with the
contacts.
Line 4 Line
5
Relay
CR1 N.O. Contact CR1 N.C. Contact CR1
De-Energized LIGHT
IS _______ LIGHT IS _______
Energized LIGHT IS _______ LIGHT
IS _______
Let’s
next look at some relay logic:
A. The
contacts on line 8 and 9 form an OR gate in junction with the green light
on line 8.
B. The contacts on line 10 form an AND
gate in junction with the red light on
line 10.
C. The contacts on line 11 and 12 form an
OR gate in which one input must be
de-energized.
D. The contacts on line 13 form an AND gate
in which one input must be
de-energized.
E. The contacts on line 14 and 15 form an exclusive
OR gate.
Using
the attached form, make a truth table for each of the five gates.
NOTE: De-Energized (‘off’) is shown as 0. Energized (‘on’) is shown as 1.
3. Now make the dotted contact connections in
the circuit. Don’t forget to turn off
the circuit breaker while making the control wiring change. Observe what happens when you energize relay
CR1.
What
happened differently from before?
The
added contact is commonly referred to as a "Seal in contact." Why is this so?
When
would a seal in contact be desirable?
Answer
questions and fill in lab as directed.
When you have done this, disconnect your circuit and put the trainer
away. Turn in your lab before you leave.

